Comparison Of Star/Delta and Zig-zag/Star Transformer Based
DSTATCOM For Power Quality Improvement
Guided BY- Submitted By-Monika Jain Anurag Jain Asst. Professor (0105EE13MT02)EX Department, OIST Bhopal
Content • Introduction• Literature Review• Single line diagram of Proposed system for Star/Delta transformer• Control algorithm • MATLAB model• Simulink Results• Single line diagram of Proposed system for Zig/Zag transformer • Simulink Results• Comparison • Conclusion• Appendix• Paper Published• References
Introduction
There are many factors both internal and external that affect the quality and quantity
of power that is being delivered. In present day power distribution systems are
facing severe Power Quality problems, such as poor voltage regulation, high
reactive power, harmonics, excessive neutral current, etc.
The Custom Power Devices(CPDs) are used to resolve these problems.
Power Quality
“Continuity” of supply and the “Quality” of voltage.
Power Quality is the interaction of electrical power with electrical equipment.
If electrical equipment operates correctly and reliably without being damaged or
stressed, we would say that the electrical power is of good quality.
On the other hand, if the electrical equipment malfunctions, is unreliable, or is
damaged during normal usage, we would suspect that the power quality is poor.
Power Quality Problems
Voltage sag
Voltage swell
Transient
Power Quality Problems
Harmonics
Voltage unbalance
Under voltage
Power Quality Problems
OVERVOLTAGE
VOLTAGE FLICKER
INTERRUPTION
Custom Power Devices
To improve the reliability and power quality in a distribution, a group of devices,
called Custom Power Devices (CPD) are in use now days.
DSTATCOM
DVR
UPQC
DSTATCOM
• It is a shunt connected CPD based on a power electronics Voltage Source Converter
• The distribution static compensator (DSTATCOM) is used for compensating PQ
problems in the current.
VSC• A voltage-source converter is a power electronic device, which can generate a
sinusoidal voltage with any required magnitude, frequency and phase angle.
• The VSC is used to either completely replace the voltage or to inject the
“missing voltage‟. The “missing voltage” is the difference between the
nominal voltage and the actual.
Literature Review• Bhim Singh, et.al. [2008] A new topology of three-phase four-wire DSTATCOM
consisting of a H-bridge VSC (voltage source converter) with a star/delta
transformer is proposed for power quality improvement in the distribution
systems.
• T R Somayajulu, et.al. [2008] In this paper, a new topology of DSTATCOM
(Distribution Static Compensator) is proposed for power quality improvement in a
three-phase four-wire distribution system. A three-leg VSC (Voltage Source
Converter) based DSTATCOM is integrated with a zig-zag transformer
• D.P. Kothari et.al. [2008] In this paper, a new three-phase four-wire distribution
static compensator (DSTATCOM) based on a T-connected transformer and a
three-leg voltage source converter (VSC) is proposed for power quality
improvement.
• P Jayaprakash, et.al. [2012] In this paper, a new topology of DSTATCOM using
three single-phase VSCs (voltage source converters) integrated with a zig-zag
transformer is employed for the power quality improvement in three-phase four-
wire distribution systems. The zig-zag transformer is used to providing a path to
the zero sequence fundamental as well as harmonics currents.
• Bhim singh et.al [2008] A new topology of DSTATCOM (distribution static
compensator) consisting of a H-bridge VSC (voltage source converter) and a
star/delta transformer is proposed for power quality improvement in the three-
phase four wire distribution system.
• P. Jayaprakash et.al [2008] A detailed investigation is made into the causes,
standards, and remedies of the excessive neutral current. A reduced rating voltage-
source converter with a zig-zag transformer as a distribution static compensator is
proposed for power quality improvement in the three-phase four wire distribution
system.
• Bhattacharya Sourabh, [2012] D-STATCOM (distribution static compensator) is a
shunt device which is generally used to solve power quality problems in
distribution systems. D-STATCOM is a shunt device used in correcting power
factor, maintaining constant distribution voltage and mitigating harmonics in a
distribution network.
• D.P. Kothari, et.al. [2009] A three-phase four-wire DSTATCOM (distribution
static compensator) based on three-leg VSC (voltage source converter) isolated
with a star/hexagon transformer is demonstrated for power quality enhancement in
a three-phase four-wire distribution system.
Single line diagram of Proposed system for Star/Delta transformer
Design of Star/Delta TransformerThe kVA rating of the transformer is given as
kVASD = 0.5ΣVrmsIrms
kVASD = 0.5(ΣVYrmsIYrms +ΣV∆rmsI∆rms)
For the integrated DSTATCOM configuration using a Star/Delta transformer, the rating is obtained as,Rms value is given as
√3VLIL= (kW*1000/CosФ)
kVASD = 0.5[{3*(INm/3)*(VL/√3)+3*(INm/3)*(VL/√3)}]
The rating of transformer 3.4 kVA and ratio 240/140 V are selected for the operation
Star/Delta Transformer
Such connections are used
principally where the voltage is to
be stepped down.
Star/Delta transformer connection and its Phasor diagram
Design of DSTATCOMDC Bus Voltage: The dc bus voltage is defined as,
Vdc = 2√2 VLL/(√3m)
Where m is the modulation index and is considered as 1. Thus, one may obtain the
value of Vdc as 677 V for VLL of 415 V. Thus, Vdc of the value of 680 V is selected.
DC Bus Capacitor: Dc capacitor is governed by the reduction in the dc bus voltage
Cdc[(dc) dc1)] = 3V(aI)t
where a is the over loading factor, and t is the response time of the DSTATCOM and t
is considered as 350µs .
Considering Vdc= 680 V, Vdc1= 670 V, V=415/3, a=1.2 , the calculated value of Cdc
is 2600 µf. So Cdc is chosen to be 3200 µf.
AC Inductor: The selection of the ac inductance depends on the current ripple
icr,p-p. The ac inductance is given as,
Lf = [(√3mVdc) /(12afs icr(p-p))
The value of AC Inductance is defined 5mH.
Ripple Filter: A high pass first-order filter tuned at half the switching frequency is
used to filter out the noise from the voltage at the PCC. The time constant of the
filter should be very small compared to the fundamental time period (T).
Rf Cf << T/10
Control Algorithm
Control StrategyA. Active Component of Reference Source Currents
• Three-phase voltages at the PCC are considered sinusoidal and hence their
amplitude is computed as,
Vt = {(2/3) (vSa2 +vSb
2 +vSc2)} 1/2 (1)
• The unit vector in phase with vsa, vsb and vsc are derived as,
ua = vSa/Vt; ub = vSb/Vt; uc = vSc/Vt (2)
• The error in dc bus voltage of VSC (Vdcer (n)) of an DSTATCOM at nth sampling
instant is as,
Vdcer(n) = Vdcref(n) – Vdc(n) (3)
• The output of the PI controller for maintaining dc bus voltage of the VSC at the
nth sampling instant is expressed as,
iloss(n) = iloss(n-1) + Kpd { Vdcer(n) – Vdcer(n-1)} + KidVdcer(n) (4)
• In-phase components of reference source currents are estimated as:
isad* = ua iloss ; isbd* = ub iloss ; iscd* = uc iloss (5)
B. Quadrature Component of Reference Source Currents
• The unit vectors (wa, wb and wc) in quadrature with vsa, vsb and vsc may be derived
using a quadrature transformation of the in-phase unit vectors ua, ub and uc as,
wa = -ub / √3 + uc / √3 (6)
wb = √3 ua / 2 + (ub – uc) / 2√3 (7)
wc= -√3 ua / 2 + (ub – uc) / 2√3 (8)
• The error in PCC voltage of VSC (Vser (n)) of an DSTATCOM at nth sampling
instant is as,
Vter(n) = Vtref(n) – Vt(n) (9)
• The output of the PI controller for maintaining amplitude of PCC voltage at the
nth sampling instant is expressed as,
iqr(n) = iqr(n-1) + Kpq { Vter(n) – Vter(n-1)} + KiqVter(n) (10)
• The quadrature components of reference source currents are estimated as:
isaq* = waiqr ; isbq* = wbiqr ; iscq* = wciqr (11)
• Total reference source currents are sum of in-phase and quadrature components of
the reference source currents as,
isa* = isad* +isaq* (12)
isb* = isbd* +isbq* (13)
isc* = iscd* +iscq* (14)
These reference source currents (isa*, isb* and isc*) are compared with the sensed
source currents (isa, isb and isc) in PWM current controller of VSC of DSTATCOM.
These current errors controlled using a current controlled PWM to generate gating
pulse of the switches.
MATLAB Model
Subsystem of firing algorithm
DSTATCOM consisting Star/Delta Transformer with Nonlinear Load
Source Voltage THDTHD 1.61%
Source Current THDTHD 4.69%
Load Current THDTHD 49.15%
Single line diagram of Proposed system for Zig/Zag transformer
Design of Zig/Zag TransformerConsidering a turn ratio of 1:1:1 and voltage across each winding VX volts and
line voltage is VL then,
VX = (VL / √3)
Similar to Star/Delta transformer, kVA rating of Zig/Zag transformer is given as
kVAZZ = 0.5 {ƩVzrmsIzrms)
For the integrated DSTATCOM configuration using a zig-zag / star transformer,
the rating is obtained as,
(kVA)ZZ/S = 0.5[{6*(IL)*(VL/3)} + {3*(IL)*(VL/3)}]
(kVA)ZZ/S = 0.5[{6*(15)*(140)} + {3*(15)*(140)}]
The transformer of rating 3kVA and ratio 140/140/140 V are selected.
Zig/Zag Transformer
Zig/Zag Transformer connection and its Phasor diagram
DSTATCOM consisting Zig/Zag Transformer with Nonlinear Load
Source Voltage THDTHD 1.68%
Source Current THDTHD 4.29%
Load Current THDTHD 49.33%
ComparisonS.No.
Parameter DSTATCOM Zig/Zag Star/Delta
1. kVA
12 3 3.4
2. Input Voltage 415 v, 50Hz 140 v 240 v
3. DC Voltage
700 340 340
4. DC Bus Capacitance
4000 µf 3200 µf 3200 µf
5. Transformer Required
- 140v/140v/140v 240v/140v
6. VSC
4 leg 3 leg 3 leg
7. No. of switches
8 6 6
Conclusion• The performance of system consisting DSTATCOM with Star/Delta and Zig/Zag
transformer has been demonstrated for Harmonic elimination, neutral current
compensation, and power factor correction for three-phase balanced system.
• The Proposed systems has been reduced the rating of VSC and found effective for
compensating to solve power quality issues.
• The rating of Zig/Zag transformer is lesser than the rating of Star/Delta transformer.
Appendices• AC line voltage: 415 V, 50 Hz
• Line Impedance: Rs=0.01ohm, Ls=1mH
• Load: Non-linear: Three single phase bridge rectifier with an R-L-C load with, R
= 25ohm and C = 100μF and L = 8mH
DSTATCOM Parameters:
• VSC: Six IGBTs connected as three-leg VSC
For Star/Delta transformer
• DC bus voltage: 340V
• DC bus capacitance: C= 3200μF.
• AC Inductance: Lf= 5 mH
• Three numbers of single-phase transformers of rating 3.4kVA with 240V/140V for
the system.
For Zig/Zag transformer
• DC bus voltage: 340V
• DC bus capacitance: C= 3200μF.
• AC Inductance: Lf= 5 mH
• Three numbers of single-phase transformers of 3kVA with 140 V/140 V/140V.
Paper Published • Anurag Jain and Monika Jain “Comparison of Star/Delta and Zig/Zag Transformer Based
DSTATCOM for Power Quality Improvement” 3rd IEEE International Student’s Conference on
Electrical, Electronics and Computer Science 5-6 march 2016, accepted (SCEECS-2016),
Maulana Azad National Institute of Technology (MANIT) Bhopal, India.
• Anurag Jain and Monika Jain “Isolated operation of Star/Delta and Zig/Zag transformer Based
DSTATCOM for Power Quality Improvement” National conference of Recent Advancement in
Futuristic Technologies 17-18 October 2015.
• Anurag Jain and Monika Jain “Comparative Analysis of Star/Delta and Zig/Zag Transformer
Based DSTATCOM for Power Quality improvement “International Journal of Innovative Trends
in Engineering (IJITE), ISSN: 2395-2946 IJITE_12_01403 Volume 12 No-1 December 2015.
References • [1] Bhim singh, P Jayaprakash, and D.P. Kothari, “Three-phase Four wire
DSTATCOM with H-Bridge VSC and Star/Delta Transformer for Power Quality
Improvement”. IEEE2008.
• [2] Bhattacharya Sourabh, “Applications of DSTATCOM Using
MATLAB/Simulation in Power System” ISSN 2277 - 2502 Vol. 1(ISC-2011), 430-
433 (2012) Res.J.Recent.Sci
• [3] Sai Kiran Kumar.Sivakoti, Y.Naveen Kumar, D.Archana “Power Quality
Improvement in Distribution System Using D-Statcom in Transmission Lines”
International Journal of Engineering Research and Applications (IJERA) ISSN:
2248-9622 Vol. 1, Issue 3, pp.748-752.
• [4] P Jayaprakash, Bhim singh, and D.P. Kothari, “Reduction In Rating of Voltage
Source Converter of DSTATCOM using a Zig-zag Transformer”. IEEE2012.
• [5] Bindeshwar Singh, K.S. Verma, Pooja Mishra, Rashi Maheshwari, Utkarsha
Srivastava, and Aanchal Baranwal “Introduction to FACTS Controllers: A
Technological Literature Survey” International Journal of Automation and Power
Engineering Volume 1 Issue 9, December 2012
• [6] M.Bhanu Siva, M.R.P Reddy, Ch.Rambabu “Power Quality Improvement of
Three-phase four-wire DSTATCOM with Fuzzy logic Controller” (IJCSIT)
International Journal of Computer Science and Information Technologies, Vol. 2
(5) , 2011, 2273 – 2276.
• [7] C. Sankaran, “Power Quality” CRC Press new yark 2002.
• [8] Bhim singh, P Jayprakash, T R Somayajulu, D P Kothari, Ambrish
Chandra,and Kamal-Al-Haddad, “Intgrated Three-leg VSC with a Zig-zag
Transformer based Three-phase Four-wire DSTATCOM for Power Quality
Improvement”. IEEE2008.
• [9] Akwukwaegbu I. O, Okwe Gerald Ibe ”Concepts of Reactive Power Control
and Voltage Stability Methods in Power System Network” IOSR Journal of
Computer Engineering (IOSR-JCE) e-ISSN: 2278-0661, p- ISSN: 2278-
8727Volume 11, Issue 2 (May. - Jun. 2013), PP 15-25 www.iosrjournals.org
• [10] Bhim Singh, P.Jayaprakash, T.R. Somayajulu, and D.P. Kothari, “Reduced
Rating VSC With a Zig-Zag Transformer for current compensation in a three-
phase Four-Wire Distribution system” IEEE transactions on power delivert,
vol.24.no. 1. January 2009.
• [11] Bhim Singh, V Rajagopal “Power Balance Theory Based Control of an Electronic
Load Controller for an Isolated Asynchronous Generator Driven by Uncontrolled Pico
hydro Turbine” 2009.
• [12] Ch. Siva Koti Reddy, Dr. P.Linga Reddy, “A DSTATCOM-Control Scheme for
Power Quality Improvement of Grid Connected Wind Energy System for Balanced and
Unbalanced Nonlinear Loads” International Journal of Modern Engineering Research
(IJMER) www.ijmer.com Vol.2, Issue.3, May-June 2012 pp-661-666 ISSN: 2249-6645
• [13] Sunil Kumar and Bhim Singh ”Control of 3‐Leg VSC Based 3‐Phase 4‐Wire
DSTATCOM using Modified Instantaneous Symmetrical Component Theory”
International Journal of Automation and Power Engineering (IJAPE) Volume 2 Issue 6,
September 2013.
• [14] Bhim singh, P Jayaprakash, and D.P. Kothari, “Implementation of An Isolated
Three-leg VSC with Stat/Hexagon Transformer based Three-Phase Four-wire
DSTATCOM”. Second international conference on emerging trends in engineering
and technology, ICETET-09.
• [15] A. de Almeida, L. Moreira. J. Delgado “Power Quality Problems and New
Solutions” ISR – Department of Electrical and Computer Engineering University
of Coimbra, Pólo II 3030-290 Coimbra (Portugal).
• [16] Bhim singh, P Jayaprakash, and D.P. Kothari, “isolated H-Bridge VSC based
3-phase 4-wire DSTATCOM for Power Quality improvement”. ICSET2008.
• [17] Bassy W. Kennedy, “Power Quality Primer” chaptor-2 pg no. 33 to 43.
McGraw hill new yark.