Digital Controller in a Process Control Loop
-
8/3/2019 Digital Controllers_anjan raksit
2/49
Digital Controller in a Process Control Loop
In a processor based digital controller, rapid switching from onealgorithm to another (e.g. a P controller to a PID controller) andautomatic tuning of controller parameters are possible.
No drift problem is encountered in a digital system.
All the desirable features of a process controller (e.g. anti-integralwind-up, auto/manual modes of operation with bump-less transfer
etc.) may be easily incorporated while maintaining the highaccuracy and precision of digital systems.
-
8/3/2019 Digital Controllers_anjan raksit
3/49
Digital Controller in a Process Control Loop
+ ADCDigital
ControllerDACr
+
_
e en mn
Set pointError
Errorsequence controlleroutputsequence
m FinalControlElement
VProcess
Controlleroutput
C
ADC equivalent
e en
Sampler
m
n
m
C
Sample & hold
(holdcapacitor)
DAC equivalent
e
time0
Error
en 2
n
Errorsequence
0 1 2 3
Controlleroutput
sequence
DACoutput
m
mn
0 1 2 3n
time0 2
m
Sampling interval (ADC conversion time + computation time)
-
8/3/2019 Digital Controllers_anjan raksit
4/49
Digital Controller in a Process Control Loop
The error computation may be performed digitally if the set-point is available indigital form (say, from digital keyboard) and the measured variable is digitized withthe ADC.
+rn+
DigitalController
DACen
Errorsequence
_Set pointsequence
(digital)
mn m Final
ControlElement
Process
ADCCn
outputsequence
CV
Digital System
Proper selection of the sampling interval is necessary for satisfactory operation ofthe process control loop.
A large may lead to unstable operation of the loop (because of the extra lagintroduced in the loop), whereas a very small requires a high speed digital hardware(hence high cost) to implement the controller.
-
8/3/2019 Digital Controllers_anjan raksit
5/49
Realization of Digital Controllers(through discrete approximation of analog controllers)
Proportional (P) Controller
The controller output at the nth instant is given by
n p n n n n
m K e b m b= + = +
The analog controller output is
m = Kp
e + b
where, Kp = proportional gain,bn = fixed bias.
Realization of the P controller:
Kp
+
bn
mn
en
m'n
-
8/3/2019 Digital Controllers_anjan raksit
6/49
Realization of Digital Controllers(through discrete approximation of analog controllers)
Proportional-Integral (PI) Controller
The analog controller output is
1.
t
p o
i
m K e e dt bT
= + +
= m+ b, where Ti is the integral time and1 .
t
p o
i
m K e e dt T
= +
Let the integration term be .t
o I e dt =
The integration term at the nth instant is .n
n o I e dt
= where is the sampling interval
. .n n
o ne dt e dt
= + for n = 1,2,3,..
Now,( )1
1. .n n
no oe dt e dt I
= =
Then,
-
8/3/2019 Digital Controllers_anjan raksit
7/49
t
e
( )1
t n
t n
e
e
=
=
( )1n n
This area may be approximated by the shaded rectangle (called the method of
rectangular integration) as
Pl Controller
The second term of the above relation represents the area
under the curve e for (n 1) t n.
-
8/3/2019 Digital Controllers_anjan raksit
8/49
Using the notation en for t ne = 1n n n I I e= +,
t
e
( )1
t n
t n
e
e
=
=
( )1n n
Thus,
( )1.
n
n t nedt e
=
Pl Controller
-
8/3/2019 Digital Controllers_anjan raksit
9/49
Similarly the output at the (n 1)th instant may be expressed as
1n n n I I e= +
Now, output m at the nth instant may be expressed as
where
Pl Controller
The difference between these two outputs is
( )1 1 11
n n p n n n n
i
m m K e e I I T
= +
-
8/3/2019 Digital Controllers_anjan raksit
10/49
1 1 1, say
o n n na e a e m = + +
where, 1o pi
a K T
= + and
1 pa K=
Pl Controller
or,1 11n n p p n n
i
m e K K e m
T
= + +
1 1
n
n n p n n
i
e
m m K e e T
= +
( )1 1 11
n n p n n n n
i
m m K e e I I
T
= +
Substituting the value of (I
n I
n-1) for rectangular integration, [(I
n I
n-1) = e
n]
-
8/3/2019 Digital Controllers_anjan raksit
11/49
Realization of the PI Controller
a1
ao
+
+
m'n
delay
m'n-1
bn
(bias)
mn
en-1
delay
en
errorsequence
Controlleroutput
sequence
Controller output at the nth instant:
mn= mn+ bn
mn= a0en+ a1en-1 + mn-1
Problem: Develop a digital PI Controller using Trapezoidal rule for integration.
-
8/3/2019 Digital Controllers_anjan raksit
12/49
Velocity or incremental form of PI controller
The controller output is proportional to the derivative of a standard PIcontroller and it may be expressed as (without bias):
1 1 1 1n n n n n o n nm m m m m a e a e = = = +
Velocity form of controller is useful when the actuator is some kind ofadder (integral action), like a stepping motor.
-
8/3/2019 Digital Controllers_anjan raksit
13/49
Software Realization of the PI Controller
a1
a0 + +mp
b
m
e1
e
# include < studio.h>void main (void)
{float e = 0, e1, m, mp = 0;float a0, a1, b;float adc (void) ; // digitized error
void dac (float m ) ; // analog outputa0 = - - - - - - - - ; // Kp [1 + /Ti ]a1 = - - - - -- - - ; // -Kpb = - - - - - - - - - ; // bias
-
8/3/2019 Digital Controllers_anjan raksit
14/49
Software Realization of the PI Controller
a1
a0 + +mp
b
m
e1
e
for (;;) // continuous loop{ // loop time is the sampling interval e1 = e;e = adc ();mp = mp + a0*e + a1*e1;m = mp + b;
// provision for saturationif (m < 0) m = 0;if (m > 100) m = 100;dac (m);}
}
-
8/3/2019 Digital Controllers_anjan raksit
15/49
Software Realization of the PI Controller
a1
a0 + +mp
b
m
e1
e
float adc (void) // Analog-to-digital conversion{float v;
scanf (%f, &v); // for (keyboard) simulationreturn v; // (to be replaced for actual} // realization)
void dac (float m) // Digital-to-analog conversion{
printf (%f\n, m); // for (VDU) simulation} // (to be replaced for actual realization)
-
8/3/2019 Digital Controllers_anjan raksit
16/49
-
8/3/2019 Digital Controllers_anjan raksit
17/49
PD Controller
Thus the controller output at the nth instant is
1
1
1 1
or 1
n n
n p n d n
p dd
n p n n n
o n n n
e em K e T b
K TT
m K e e b
a e a e b
= + +
= + +
= + +
where 1 do p
Ta K
= +
and
1
p dK T
a
=
-
8/3/2019 Digital Controllers_anjan raksit
18/49
Realization of the PD Controller
a1
ao
+ +
bn
(bias)
mn
en-1
delay
en
(error) Controlleroutput
Problem: Develop a c program for software realization of the PD Controller.
-
8/3/2019 Digital Controllers_anjan raksit
19/49
PD Controller
Provision for anti-derivative kick
To avoid derivative action from a sudden change in set-point, the derivative actionis generally derived from the measured output.
Now, e = r c
then, ,de dr dc
dt dt dt
=
,dc
dt= assuming set-point r is constant.
Thus, the controller output may be expressed as,
p d
dcm K e T b
dt
= +
-
8/3/2019 Digital Controllers_anjan raksit
20/49
-
8/3/2019 Digital Controllers_anjan raksit
21/49
Realization of PD Controller with anti-derivative kick
Problem: Develop a c program for software realization of the PD Controllerwith anti-derivative kick
ao
po
p1
+ +
en
error
cn
(processoutput)
cn-1
delay
bn
(bias)
mn
(Controller output)
-
8/3/2019 Digital Controllers_anjan raksit
22/49
Realization of Digital Controllers
(through discrete approximation of analog controllers)
Proportional-Integral-Derivative (PID) Controller
The analog controller output is
1
' (say)
t
p do
i
dem K e edt T b
T dt
m b
= + + +
= +
where1
't
p do
i
dem K e edt T
T dt
= + +
The controller output (without bias) at the nth instant, using backward differencealgorithm, is
1n n nn p n d
i
I e em K e T
T
= + +
-
8/3/2019 Digital Controllers_anjan raksit
23/49
-
8/3/2019 Digital Controllers_anjan raksit
24/49
( )11 1 2 12n n d
n n p n n n n n
i
I I T m m K e e e e e
T
= + + +
Using rectangular integration algorithm, 1n n n I I e =
then, ( )1 1 1 22d
n n p n n n n n n
i
Tm m K e e e e e e
T
= + + +
or,1 2 1
21 1
p dd dn n p n p n n
i
K TT Tm e K e K e m
T
= + + + + +
or, 1 1 2 2 1n o n n n nm a e a e a e m = + + +
PID Controller
-
8/3/2019 Digital Controllers_anjan raksit
25/49
1 1 2 2 1n o n n n nm a e a e a e m = + + +
1
1
2 1
do p
i
dp
Ta KT
Ta K
= + +
= +
where,
and2
p dK Ta
=
PID Controller
-
8/3/2019 Digital Controllers_anjan raksit
26/49
Realization of the PID Controller
1 1 2 2 1n o n n n nm a e a e a e m = + + +
a
2
a1
ao
+ +
bn
(bias)
mn
m'n-1
m'n
en-2
en-1
en
mn = mn + bnand
-
8/3/2019 Digital Controllers_anjan raksit
27/49
-
8/3/2019 Digital Controllers_anjan raksit
28/49
Techniques used for anti-integral windup
By saturating or limiting the integral value
By resetting the integral value to zero
By omitting the integral term
By adaptive adjustment of controller parameters
-
8/3/2019 Digital Controllers_anjan raksit
29/49
Some anti-integral windup schemes
Stop integration when PI/PID controller internal output (prior to thesaturation block) exceeds the saturation limits
+ Kp +100
1000Process
+_
+
n
Saturation
r e
+_
X
Multiplier
0
11/0
Stop integration ifsaturated
C
Scheme for PI Controller
hardswitching Scheme
i
p
sT
K
-
8/3/2019 Digital Controllers_anjan raksit
30/49
+ Kp +100
1000Process
+
_+
n
Saturation
r e
+_
X
Multiplier
0
11/0
Stop integration ifsaturated
C
Scheme for PI Controller
hardswitching Scheme
i
p
sT
K
Performance of anti-integral windup scheme
PI control without anti-integral windup PI control with anti-integral windup
-
8/3/2019 Digital Controllers_anjan raksit
31/49
Some anti-integral windup schemes
Reduce integration gradually as PI/PID controller internal outputexceeds the saturation limits
+ Kp +100
1000Process
+_
+
Saturation
r e
+_
p
i
K
T
C
softswitching Scheme
+
G
G : a constant
s
1
-
8/3/2019 Digital Controllers_anjan raksit
32/49
Some anti-integral windup schemes
Clegg integrator the integrator is set to zero (reset) when the errorcrosses zero
_
+
C
reset control
resetSW
error integrator outputR
-
8/3/2019 Digital Controllers_anjan raksit
33/49
-
8/3/2019 Digital Controllers_anjan raksit
34/49
Automatic/Manual modes of Operations
ControllerFinal
Control element
Manual input or commnd
Auto
Man
me
error
vProcess
If there is any difference between the controller output and the manual command, abumpoccurs in the process output when the switch position is altered.
To provide bump-less transferfrom auto-to-manual change over, specialarrangements may be made for set-point initialization.
The manual command is driven to equal the controller output when the loop is inAUTO mode.
-
8/3/2019 Digital Controllers_anjan raksit
35/49
Automatic/Manual modes of Operations
ControllerFinal
Control element
Manual input or commnd
Auto
Man
me
error
vProcess
When the loop is in MANual mode, if there is a steady error existing due to anydifference between the set-point of the controller and the process output (under
manual control), integral term, in case of PI and PID controllers, may wind-up to alarge value, and consequently anti-integral wind-up is necessary for suchsituations.
To provide bump-less transferfor all the operating modes, incremental or velocityfrom of controller is used with an additional integrator.
-
8/3/2019 Digital Controllers_anjan raksit
36/49
-
8/3/2019 Digital Controllers_anjan raksit
37/49
-
8/3/2019 Digital Controllers_anjan raksit
38/49
Automatic/Manual modes of Operations
Digital
incremental
controller
Integrator
Incremental manual command
Auto
Man
m'ne
n +
bn
(bias)
m'n m
n
Scheme for bump-less transfer
The presence of integrator at the output ensures a smooth output variation even
when the actual manual command is different from the actual controller outputunder closed-loop control.
-
8/3/2019 Digital Controllers_anjan raksit
39/49
Realization of the incremental type PID Controller
a
2
a1
ao
+ +
bn
mn
m'n-1
m'n
en-2
en-1
en +
m'n
Incremental manualCommand
MAN
AUTO
Incremental orVelocity
Controller
Integrator
-
8/3/2019 Digital Controllers_anjan raksit
40/49
Automatic tuning of PID Controllers the Relay autotuner
This is based on a special technique for determining the critical gain Kc and critical
time period Tc of the process loop.
Kc is the gain margin of the process loop.
Controller parameters Kp, Ti and Td are calculated according to Ziegler Nichols(Z-N) rulefor a stable time response.
Suitable for processes with non-zero dead-time.
Z-N settings
gain margin: 2
Controller Kp Ti Td
P Controller 0.5 Kc
PI Controller 0.45 K c Tc/1.2
PID Controller 0.6 Kc Tc/2 Tc/8
-
8/3/2019 Digital Controllers_anjan raksit
41/49
Automatic tuning of PID Controllers the Relay autotuner
The critical gain Kc and critical time period Tc are determined from an experimentwith relay (switching element) feedback.
+
-D
0
D
Processe v
Relay
r = 0
set pointc+
_
The relay control provides ON / OFF control of the process.
The input r is set to zero.
The output c oscillates around a mean value of zero (limit-cycle oscillations).
The process is driven by a square wave of amplitude D.
-
8/3/2019 Digital Controllers_anjan raksit
42/49
Automatic tuning of PID Controllers the Relay autotuner
+
-D0
D
Processe v
Relay
r = 0
set pointc+
_
Assuming the process to be a low-pass system, the process output c containsmainly the fundamental component.
Thus the error signal e becomes sinusoidal,
e = A sint
-
8/3/2019 Digital Controllers_anjan raksit
43/49
Automatic tuning of PID Controllers the Relay autotuner
The relay output v may be found out as follows:
+
-D0
D
Processe v
Relay
r = 0set point
c+
_
v
D
0e
- D
time
e0 A
- A
v
D
0time
- D
2
2
e = A sint
-
8/3/2019 Digital Controllers_anjan raksit
44/49
Automatic tuning of PID Controllers the Relay autotuner
+
-D0
D
Processe v
Relay
r = 0set point
c+
_
D
- D
2
v
time
The Fourier series of the relay output (v) may be expressed as:
4 1 1sin sin 3 sin 5 .......3 5
Dv t t t
= + + +
The process practically attenuates all higher harmonics other than the fundamental.
Then the process gain at frequency becomes
( )
4 4
output amplitude A AG
Dinput amplitude D
= = =
-
8/3/2019 Digital Controllers_anjan raksit
45/49
Automatic tuning of PID Controllers the Relay autotuner
+
-D0
D
Processe v
Relay
r = 0set point
c+
_
( )
44
output amplitude A AG
Dinput amplitude D
= = =
Process gain at frequency :
Now, to maintain steady oscillations at = c, the loop gain is 1 (consideringnegative feedback).
Thus the gain of the relay controller (i.e. the critical gain) at = c is
( )( )c c
1 4as K . G 1
c
c
DK
AG
= = =
Also G (c) = , as relay phase shift is zero.
.
-
8/3/2019 Digital Controllers_anjan raksit
46/49
Automatic tuning of PID Controllers the Relay autotuner
+
-D0
D
Processe v
Relay
r = 0set point
c+
_
Thus by knowing the relay amplitude D and by measuring the amplitude A of the
process output c, critical gain Kc may be determined .
4
c
D
K A
=
Tc may be estimated by measuring the frequency of the output oscillation .2
c
c
T
=
-
8/3/2019 Digital Controllers_anjan raksit
47/49
Block diagram of the Relay autotuner
D
0
D
Relay
+PID
ControllerProcess
Manualcommand
r +
_
eM
A v
T
c
Modeswitch
M Manual positionA Auto positionT Tune position
(The Satt Control Autotuner by Satt Control, Sweden)
At first, the process is brought to equilibrium state ( zero error), bysetting a constant control signal in manual mode.
The tuning is then activated by pushing the mode switch to tune position.
-
8/3/2019 Digital Controllers_anjan raksit
48/49
Modified relay characteristic for a non-zero set-point
Manualsetting
v
0e
v
0t
Controlleroutput forzero error
D = 0.1vmax
The relay amplitude D is initially set to 10% of the controller output-range.
This amplitude is adjusted after one and a half period to give oscillation of 2% of the mean output.
This ensures minimum disturbance at the process output due to tuning.
This adjustment is done by measuring the change in output during the first one and a half period.
The modified relay amplitude is stored for the next tuning operation.
-
8/3/2019 Digital Controllers_anjan raksit
49/49
D0
D
Relay
+PID
ControllerProcess
Manualcommand
r +
_
eM
A v
T
c
Modeswitch
M Manual positionA Auto positionT Tune position
The system is automatically switched to Auto mode after estimating the
critical gain Kc and critical time period Tc during first 5 period of oscillation.
The parameters of PID controller (viz. Kp, Ti and Td ) are determined from Kcand Tc according to Z-N rule.
Satt Control Autotuner