INSPECTION OF M&E FIRE
SAFETY WORKS
PRESENTED BY: SIEW YEE CHEONG
-
8/13/2019 SIEW_RI ME
2/55
Topics to be Covered1) Obstruction to Sprinklers
2) Fire Rated Duct
3) Fire Rated Pipe
4) Auto and Manual Start/Stop of MV Fans
5) Auto and Manual Start of Engineered Smoke Control System
6) Hot Smoke Test
-
8/13/2019 SIEW_RI ME
3/55
Obstruction to Sprinklers Vertical Obstruction (Large Duct, Deep Beam, Drop Ceiling)
Sprinklers at Close Spacing
Plan Obstruction
Royal Flash Sprinkler
-
8/13/2019 SIEW_RI ME
4/55
Fire source
Coverage Areaoverlapped by
sprinklers
S S
Wall
< S
-
8/13/2019 SIEW_RI ME
5/55
Fire
source
Area under
duct is not
protected
Coverage
Area
overlapped
by sprinklers
S S
S S
-
8/13/2019 SIEW_RI ME
6/55
Sprinklers blocked by
deep beam
(insufficient coverage)
Fire
source
Coverage
Area
overlapped
by
sprinklers
S S
All areas
fullyprotected by
sprinklers
Supplementary
sprinklers
under beam
Fire
source
S S
Deep Beam Obstruction
-
8/13/2019 SIEW_RI ME
7/55
Fire
source
S S
Partial Area
not
protected
Fire
source
-
8/13/2019 SIEW_RI ME
8/55
-
8/13/2019 SIEW_RI ME
9/55
Plan Obstruction
-
8/13/2019 SIEW_RI ME
10/55
After Rectification Works
Adjusted and added sprinklers to the 4 cubicle at sensory room
-
8/13/2019 SIEW_RI ME
11/55
Royal Flash Sprinkler
-
8/13/2019 SIEW_RI ME
12/55
Royal Flash Sprinkler
Sprinkler Point
-
8/13/2019 SIEW_RI ME
13/55
Fire Rated Duct
(Ventilation, Kitchen Exhaust and Smoke Extract Duct)
Proprietary System
a) Cladded on steel duct using building boards (mainly calcium silicate
based) of various thickness and density with mineral wool insulationb) Sprayed on steel duct with thick vermiculate spray (Vermiduct)
c) Sprayed on steel duct with fine vermiculate spray (Flambar BW11)
-
8/13/2019 SIEW_RI ME
14/55
Fire Rated Duct Installation
General Requirements
To be provided for smoke control system, kitchen exhaust system (horizontal
duct only) and ducts serving special occupancies where fire dampers are not
permitted. eg., FCC, fire pump room, generator room, and etc. Same fire resistance rating as the wall/ floor unless otherwise stated.
PE Certificate of Supervision for Special Materials.
-
8/13/2019 SIEW_RI ME
15/55
Fire Rated Duct Installation
Typical non-compliance
Use of non-approved system.
Fire rated duct suspended from non-fire rated structure.
Perforations and penetrations by other services for cladded on duct.
Other ducts or service running directly above fire rated ducts.(Fire rated duct used to support other services)
Workmanship and supervision of construction integrity.
Hatch opening not properly constructed.
Product without Certificate of Compliance (COC)
-
8/13/2019 SIEW_RI ME
16/55
Fire Rated Duct Installation
a. Cladded on steel duct using building boards (mainly calcium silicate based)
of various thickness and density with mineral wool insulation.
-
8/13/2019 SIEW_RI ME
17/55
Fire Rated Duct Installation
-
8/13/2019 SIEW_RI ME
18/55
Fire Rated Duct Installation
b. sprayed on steel duct with thick vermiculate spray (Vermiduct)
-
8/13/2019 SIEW_RI ME
19/55
Fire Rated Duct Installation
c. sprayed on steel duct with fine vermiculate spray (Flambar BW11)
-
8/13/2019 SIEW_RI ME
20/55
Fire Rated Pipe(dry or wet riser) proprietary system
a) Cladded on steel pipe using building calcium silicate boards
b) Cladded on steel pipe using vermiculate boards
c) Sprayed on steel pipe using vermiculate mortar
-
8/13/2019 SIEW_RI ME
21/55
Fire Rated Pipe Installation
-
8/13/2019 SIEW_RI ME
22/55
Fire Rated Pipe Installation
Cladded on steel pipe using calcium silicate boards
-
8/13/2019 SIEW_RI ME
23/55
Fire Rated Pipe InstallationSprayed on steel pipe using vermiculate mortar
-
8/13/2019 SIEW_RI ME
24/55
Any non-compliance?
-
8/13/2019 SIEW_RI ME
25/55
Any non-compliance?
-
8/13/2019 SIEW_RI ME
26/55
Dry riser located outside stair
-
8/13/2019 SIEW_RI ME
27/55
Any non-compliance?
-
8/13/2019 SIEW_RI ME
28/55
Mechanical Ventilation System for Stair, Internal
Exit Passage and Smoke Stop Lobby
General Requirements
MV to be provided if Natural Ventilation is not available or not adequate.
-
8/13/2019 SIEW_RI ME
29/55
Mechanical Ventilation System for Stair, Internal
Exit Passage and Smoke Stop Lobby
System requirements Independent system.
Supply mode.
10 air-change/ hour for lobby.
Riser in separate masonry shaft.
Fans connected to emergency power supply.
5m separation distance from other exhaust discharge.
Horizontal duct outside staircase/ passage by fire rated duct.
Activate by building fire alarm system; and manual remote starting at FCC/ MAP.
For lobby system, vertical fire dampers can be provided at shaft openings
-
8/13/2019 SIEW_RI ME
30/55
Mechanical Ventilation System for Stair, Internal
Exit Passage and Smoke Stop Lobby
-
8/13/2019 SIEW_RI ME
31/55
Staircase Pressurisation System
General Requirement
Internal stair in building exceeding 24m in height.
Basement stair serving more than 4 storey.
Specifically required by FSSD.
-
8/13/2019 SIEW_RI ME
32/55
Staircase Pressurisation SystemSystem requirements
Activate automatically upon building fire alarm.
Manual start/stop and status monitoring at FCC/ MAP.
Fans to be connected to emergency power supply. Maintain pressure gradient such that the pressure at the exit stair is higher
than the smoke stop lobby, pressure differential around 50 Pascal.
Force to open any door not exceeding 110N.
Air velocity across door opening with 2 doors from any 2 successive storeysand the main discharge door fully open at least 1m/s.
5m separation distance.
Distribution of Pressurisation air.
Relief device.
-
8/13/2019 SIEW_RI ME
33/55
Staircase Pressurisation System
-
8/13/2019 SIEW_RI ME
34/55
Staircase Pressurisation System
-
8/13/2019 SIEW_RI ME
35/55
Staircase Pressurisation System
-
8/13/2019 SIEW_RI ME
36/55
Staircase Pressurisation System
-
8/13/2019 SIEW_RI ME
37/55
Staircase Pressurisation System
-
8/13/2019 SIEW_RI ME
38/55
Staircase Pressurisation System
-
8/13/2019 SIEW_RI ME
39/55
Staircase Pressurisation System
-
8/13/2019 SIEW_RI ME
40/55
Staircase Pressurisation System
-
8/13/2019 SIEW_RI ME
41/55
Staircase Pressurisation System
-
8/13/2019 SIEW_RI ME
42/55
Staircase Pressurisation System
-
8/13/2019 SIEW_RI ME
43/55
Staircase Pressurisation System
-
8/13/2019 SIEW_RI ME
44/55
Staircase Pressurisation System
-
8/13/2019 SIEW_RI ME
45/55
Basement Carpark Smoke Purging System
(Conventional Ducted Design)
General Requirement
For basement carpark with total floor areas exceeding 2000 sq.m.
-
8/13/2019 SIEW_RI ME
46/55
Basement Carpark Smoke Purging System
System requirements
Independent system.
Smoke purging rate at 9 air change/ hour (normal MV requirement at6 air change/ hour.
Activate automatically by building fire alarm.
Manual starting/ stopping and status monitoring at FCC/ MAP.
Interlocking of FA and EA fans. No FA fans if opening is larger than2.5% of floor area.
5m separation distance.
Exhaust ducts constructed of 1.2mm thick gauge sheet and no firedampers.
-
8/13/2019 SIEW_RI ME
47/55
Atrium Smoke Control System
General Requirement
Applicable only for Atrium
Building to be sprinkler protected
-
8/13/2019 SIEW_RI ME
48/55
Atrium Smoke Control SystemSystem requirements
Engineered design system.
Usually involves multi-scenarios. (Auto start by dedicated smoke detector)
Performance specification to maintain smoke layer at not less than 2.5mabove floor. Fire size depending on occupancy.
Adequate low level fresh air intake for replenishment.
May be in the form of natural vents (with fail safe feature) or mechanicalextraction (with excess capacity and emergency power.
Compliance with other prescription requirements of Cl. 7.6.
Status monitoring Fans, Smoke Vent, Smoke Curtain, Replacement air inlet. Manual start based on selected scenarios.
-
8/13/2019 SIEW_RI ME
49/55
Manual Start/Stop of MV Fans
General Requirement
(stair MV , stair pressurization, carpark smoke purging, STL/FFL MV)
A manual start-stop switch to be made available to firemen at FCC or MAP
System Requirements
Switch to over-ride fire alarm signal.
Ability to manual start without fire alarm signal.
Auto re-starting of fans upon change to emergency power under fire alarmcondition.
Fans should not auto reset upon resetting of fire alarm.
-
8/13/2019 SIEW_RI ME
50/55
Manual start of Engineered Smoke Control System
General Requirement A remote manual activation and control switches to be provided at
FCC or MAP
System requirements Manual activation according to design scenarios.
No requirement to manual stop the fans or close smoke vents during smokedetector activation condition.
Auto re-starting of fans upon change to emergency power under smokedetector activation condition.
Fans, smoke curtains, smoke vents & etc should not auto reset uponresetting of smoke detector.
Fans may not re-start upon change to emergency power if there is no firealarm condition.
-
8/13/2019 SIEW_RI ME
51/55
Manual start of Engineered Smoke Control System
-
8/13/2019 SIEW_RI ME
52/55
Manual start of Engineered Smoke Control System
-
8/13/2019 SIEW_RI ME
53/55
Garden by the Bay
-
8/13/2019 SIEW_RI ME
54/55
PB DesignNon-compliances include the following
Travel Distance
Exit Capacity
Exit Discharge
Engineering smoke Control Design
Omission of Sprinkler Protection below envelope
Unprotected elevated walkways (cool moist conservatory only)
-
8/13/2019 SIEW_RI ME
55/55
Duties of RI (M&E) Review the FEDB, FER and Engineering smoke control design agreed by fire
size at the gardens are 3 MW (for Christmas tree fire) and 1 MW (for rubbish
fire in flower field)
Carry out physical test of the smoke scenario, ie., smoke detection by
aspirating smoke detector, opening of sunshield, smoke vents, replacementair inlet, tripping of AHU and signal to FCC
Test the manual start function
Witness hot smoke test