Technology in ArchitecturesTechnology in ArchitecturesLecture 8

Cooling LoadsCooling Degree Hours

Energy Performance RatingsAnnual Fuel Consumption

Page 2: A4372S11_08_CoolingLoads (1).ppt

Cooling LoadsCooling LoadsComputed for worst case scenario: Late summer afternoon

at outdoor design dry bulb temperature

Include: Insolation from sun Heat gain from people,

lights, and equipment Infiltration in residential

buildings Ventilation in

nonresidential buildings

SR-3

Page 3: A4372S11_08_CoolingLoads (1).ppt

Summer Design ConditionsSummer Design ConditionsDesign Dry Bulb TemperatureMean Daily Range

S(10): T.B.1,p. 1496

Page 4: A4372S11_08_CoolingLoads (1).ppt

Determine Design Equivalent Determine Design Equivalent Temperature Difference Temperature Difference

(DETD)(DETD)Construction type Outdoor design temperatureMean daily range

L: 0-16ºFM: 16-25ºF

H: 25+ºF

S: p. 1653, T.F.5

Page 5: A4372S11_08_CoolingLoads (1).ppt

Determine Envelope U-Determine Envelope U-valuesvalues

Calculate ΣR and then find U for walls and roofs.

Note: this method ignores floors, doors, and window U-values

Page 6: A4372S11_08_CoolingLoads (1).ppt

Determine DCLFDetermine DCLFGlazing TypeDesign TemperatureShadingOrientation

S: p. 1655, T.F.6

Page 7: A4372S11_08_CoolingLoads (1).ppt

Determine Area QuantitiesDetermine Area QuantitiesPerform area takeoffs for all building envelope surfaces on each facade:

gross wall areawindow areadoor areanet wall area

4’

Elevation

4’

12’

100’

8’

1200 sf

64 sf

368 sf

768 sf

--

Page 8: A4372S11_08_CoolingLoads (1).ppt

InfiltrationInfiltration

S: p. 1657, T.F.7

Page 9: A4372S11_08_CoolingLoads (1).ppt

Ventilation AnalysisVentilation AnalysisNon-residential buildings use ventilation to

provide fresh air and to offset infiltration effects.

ASHRAE Standard 62-2001 (S: p. 1598, T.E.25)

Estimates the number of people/1000 sf of usage typePrescribes minimum ventilation/person for usage type

Page 10: A4372S11_08_CoolingLoads (1).ppt

ASHRAE 62-2001ASHRAE 62-2001Defines space occupancy and ventilation loads

S: p. 1639, T.E.25

Page 11: A4372S11_08_CoolingLoads (1).ppt

Ventilation—Sensible CLFVentilation—Sensible CLF

S: 1657, T.F.7

Page 12: A4372S11_08_CoolingLoads (1).ppt

People — Sensible GainPeople — Sensible GainDetermine number of people Activity level

S: p. 1657, T.F.8

Page 13: A4372S11_08_CoolingLoads (1).ppt

LightsLightsDetermine wattage of lighting/square foot ASHRAE 90.1 prescriptive levels Count fixture loads and add together

Note: add 15% for ballasts where applicable (e.g., fluorescent lights)

Page 14: A4372S11_08_CoolingLoads (1).ppt

EquipmentEquipmentDetermine operating wattage of equipment/square foot ASHRAE 90.1 prescriptive levels Count actual loads and add together

Note: include a diversity factor (20-30%) if specific usage patterns are unknown.

Page 15: A4372S11_08_CoolingLoads (1).ppt

EquipmentEquipmentUse manufacturer’s data or other references to obtain heat gain data.

Standby mode Copiers Monitors Printers CPU “energy star”

S: p. 1658, T.F.9

Page 16: A4372S11_08_CoolingLoads (1).ppt

Latent LoadLatent LoadNot calculated separately:

Apply a factor as a percentage of the total sensible cooling load

Dry climates: 20%Moist/Humid climates: 30%

Page 17: A4372S11_08_CoolingLoads (1).ppt

Cooling Load Example Cooling Load Example ProblemProblem

Building: Office BuildingLocation: Salt Lake City

Building: 200’ x 100’ (2 stories, 12’-6” each)

Uwall= 0.054 Btuh/sf-ºFUroof= 0.025 Btuh/sf-ºF

Page 18: A4372S11_08_CoolingLoads (1).ppt

Cooling Load Example Cooling Load Example ProblemProblemDetermine Building Envelope Areas (SF)

Building: 200’ x 100’ (2 stories, 12’-6” each)

N E S WGross Wall 5,000 2,500 5,000 2,500Windows 1,000 500 2,000 500Doors 20 20 50 20Net Wall 3,980 1,980 2,950 1,980

Roof/Floor Slab 20,000

Page 19: A4372S11_08_CoolingLoads (1).ppt

Determine Design Equivalent Determine Design Equivalent Temperature Difference Temperature Difference

(DETD)(DETD)Roof Construction type: Light color, vented, ceilingDesign temperature: 95ºFMean daily range: 32ºF

L:0-16ºFM: 16-25ºFH: 25+ºF

DETD=31.0ºF

S: p. 1653, T.F.5

Page 20: A4372S11_08_CoolingLoads (1).ppt

Cooling LoadsCooling LoadsInsert roof values

SR-3

0.025 20,000 31.0 15,500 15,500

Page 21: A4372S11_08_CoolingLoads (1).ppt

Determine Design Equivalent Determine Design Equivalent Temperature Difference Temperature Difference

(DETD)(DETD)Wall Construction type (see given) Design temperature: 95ºFMean daily range: 32ºF

L: 0-16ºFM: 16-25ºF

H: 25+ºF

DETD=11.3ºF

S: p. 1653, T.F.5

Page 22: A4372S11_08_CoolingLoads (1).ppt

Cooling LoadsCooling LoadsInsert roof values

Insert wall values

SR-3

0.025 20,000 31.0 15,500 15,500

N 0.054 3,980 11.3 2.429E 0.054 1,980 11.3 1.208S 0.054 2,950 11.3 1,800W 0.054 1,980 11.3 1,208 6,645

Page 23: A4372S11_08_CoolingLoads (1).ppt

Glazing TypeDesign TemperatureShadingOrientation

Determine Window DCLFDetermine Window DCLF

S: p. 1656, T.F.6.B

Page 24: A4372S11_08_CoolingLoads (1).ppt

Cooling LoadsCooling LoadsInsert roof values

Insert wall values

Insert glass values

SR-3

0.025 20,000 31.0 15,500 15,500

N 0.054 3,980 11.3 2.429E 0.054 1,980 11.3 1.208S 0.054 2,950 11.3 1,800W 0.054 1,980 11.3 1,208 6,645

N 1,000 14 14,000E 500 35 17,500S 2,000 20 40,000W 500 35 17,500

89,000

Page 25: A4372S11_08_CoolingLoads (1).ppt

ASHRAE 62-2001ASHRAE 62-2001Defines space occupancy and ventilation loads

S: p. 1639, T.E.25

Page 26: A4372S11_08_CoolingLoads (1).ppt

Ventilation Load — Sensible Ventilation Load — Sensible

40,000 sf x 5people/1,000sf = 200 people

200 people x 17 cfm/person = 3,400 cfm

Page 27: A4372S11_08_CoolingLoads (1).ppt

Ventilation Load — Sensible Ventilation Load — Sensible CLF CLF

Design Temperature: 95ºFCommercial Building: Ventilation

S: p. 1657, T.F.7

Page 28: A4372S11_08_CoolingLoads (1).ppt

Cooling LoadsCooling LoadsInsert roof values

Insert wall values

Insert glass values

Insert outdoor air values

SR-3

0.025 20,000 31.0 15,500 15,500

N 0.054 3,980 11.3 2.429E 0.054 1,980 11.3 1.208S 0.054 2,950 11.3 1,800W 0.054 1,980 11.3 1,208 6,645

N 1,000 14 14,000E 500 35 17,500S 2,000 20 40,000W 500 35 17,500

89,000

N/A N/A N/A

3,400 22.0 74,800 74,800

Page 29: A4372S11_08_CoolingLoads (1).ppt

People — Sensible GainPeople — Sensible GainDetermine number of people: 280Activity level: moderately active office work

S: p. 1657, T.F.8

Page 30: A4372S11_08_CoolingLoads (1).ppt

Cooling LoadsCooling LoadsInsert roof values

Insert wall values

Insert glass values

Insert outdoor air values

Insert people values

SR-3

0.025 20,000 31.0 15,500 15,500

N 0.054 3,980 11.3 2.429E 0.054 1,980 11.3 1.208S 0.054 2,950 11.3 1,800W 0.054 1,980 11.3 1,208 6,645

N 1,000 14 14,000E 500 35 17,500S 2,000 20 40,000W 500 35 17,500

89,000

N/A N/A N/A

3,400 22.0 74,800 74,800

200 250 50,000

Page 31: A4372S11_08_CoolingLoads (1).ppt

Lighting LoadLighting LoadLighting load: 1.5 w/sfEquipment load: 0.5 w/sf

Page 32: A4372S11_08_CoolingLoads (1).ppt

Cooling LoadsCooling LoadsInsert roof values

Insert wall values

Insert glass values

Insert outdoor air values

Insert people values

Insert lighting values

Insert equipment values SR-3

0.025 20,000 31.0 15,500 15,500

N 0.054 3,980 11.3 2.429E 0.054 1,980 11.3 1.208S 0.054 2,950 11.3 1,800W 0.054 1,980 11.3 1,208 6,645

N 1,000 14 14,000E 500 35 17,500S 2,000 20 40,000W 500 35 17,500

89,000

N/A N/A N/A

3,400 22.0 74,800 74,800

200 250 50,000

40,000 1.5 204,780

40,000 0.5 68,260 323,040

Page 33: A4372S11_08_CoolingLoads (1).ppt

Cooling LoadsCooling LoadsSensible Heat Gain: 508985 Btuh

Latent Heat Gain (20%): 101,797 Btuh

Total Heat Gain:610,782Btuhor50.9 Tons

Tons=Q/12,000SR-3

0.025 20,000 31.0 15,500 15,500

N 0.054 3,980 11.3 2.429E 0.054 1,980 11.3 1.208S 0.054 2,950 11.3 1,800W 0.054 1,980 11.3 1,208 6,645

N 1,000 14 14,000E 500 35 17,500S 2,000 20 40,000W 500 35 17,500

89,000

N/A N/A N/A

3,400 22.0 74,800 74,800

200 250 50,000

40,000 1.5 204,780

40,000 0.5 68,260 323,040

508,985101,797610,78250.9

2.5

1.1

14.6

16.783.352.8

12.3

100.0

Page 34: A4372S11_08_CoolingLoads (1).ppt

Cooling Degree HoursCooling Degree Hours

Page 35: A4372S11_08_CoolingLoads (1).ppt

Cooling Degree HoursCooling Degree HoursRelative indicator of warmth

S(10): T.B.1,p. 1513

Page 36: A4372S11_08_CoolingLoads (1).ppt

Cooling Degree HoursCooling Degree HoursBalance Point Temperature (BPT): temperature above which cooling is needed

CDH(BPT)= ODBT-BPT

If temperature (ODBT)=91ºF

CDH74 =ODBT-74=91-74=17 cooling degree-hours

Page 37: A4372S11_08_CoolingLoads (1).ppt

Energy Performance RatingsEnergy Performance Ratings

Page 38: A4372S11_08_CoolingLoads (1).ppt

Performance RatingsPerformance RatingsCOP: coefficient of performanceEER: energy efficiency at full loadSEER: seasonal energy efficiency

ratio

Note:SEER≈COP x 3.413

Page 39: A4372S11_08_CoolingLoads (1).ppt

Annual Fuel ConsumptionAnnual Fuel Consumption

Page 40: A4372S11_08_CoolingLoads (1).ppt

Annual Fuel Usage (E)Annual Fuel Usage (E)E= UA x CDH(BPT)

SEER

where:UA: cooling load/ºFCDH(BPT): degree hours for balance pointSEER: seasonal energy efficiency rating

Page 41: A4372S11_08_CoolingLoads (1).ppt

Calculating UACalculating UAQTotal= UA x ΔT

UA= QTotal/ΔT

From earlier example:QTotal= 610782 Btuh ΔT= 95-75=20ºF

UA=610782/20= 30,539 Btuh/ºF

Page 42: A4372S11_08_CoolingLoads (1).ppt

Annual Fuel Usage ExampleAnnual Fuel Usage ExampleCompare two systems to determine what is the expected annual electrical usage for an apartment in Salt Lake City if its peak cooling load is 12,000 Btuh?

UA=Q/ΔTUA=12,000/20= 600 Btuh/ºF

Page 43: A4372S11_08_CoolingLoads (1).ppt

Determine SEERDetermine SEERObtain SEER from manufacturer’s data or Convert COP to SEER

SEER: 5-15

For this example:SEER1=6.8SEER2=10.2

Page 44: A4372S11_08_CoolingLoads (1).ppt

Annual Fuel Usage — Annual Fuel Usage — Electricity Electricity

E= UA x CDH74 SEER

E1 =(600)(9,898)/(6.8) =873,353 wh/yr=873 kwh/yr

If electricity is $0.0735/kwh, thenannual cost = $64

Page 45: A4372S11_08_CoolingLoads (1).ppt

Annual Fuel Usage — Annual Fuel Usage — Electricity Electricity

E= UA x CDH74 SEER

E2 =(600)(9,898)/(10.2)=582,235 wh/yr =582 kwh/yr

If electricity is $0.0735/kwh, thenannual cost = $43

Page 46: A4372S11_08_CoolingLoads (1).ppt

Simple Payback AnalysisSimple Payback Analysis

Page 47: A4372S11_08_CoolingLoads (1).ppt

Simple PaybackSimple PaybackCooling System Cost Comparison

FirstCost

($)

System 1 500System 2 600

Page 48: A4372S11_08_CoolingLoads (1).ppt

Simple PaybackSimple PaybackCooling System Cost Comparison

First Annual Incremental Incremental SimpleCost Fuel Cost First CostAnnual Savings Payback

($) ($/yr) ($) ($/yr) (yrs)

System 1 500 64 --- --- ---System 2 600 43 100 21 4.8

Payback exceeds 3 years, select system 1Other factors?